DZ47N-63 MINI CIRCUIT BREAKER
Electrical Features
Rated current In :1,2,3,4,6,10,16,20,25,32,40,50,63A
Poles:1P, 1P+N, 2P, 3P, 3P+N,4P
Rated voltage Ue:240/415V
Insulation voltage Ui :500V
Rated frequency:50/60Hz
Rated breaking capacity :6000/10000A
Energy limiting class:3
Rated impulse withstand voltage(1.2/50) Uimp:4000V
Dielectric test voltage at ind. Freq. for 1 min:2kV
Pollution degree:2
Thermo-magnetic release characteristic: B,C,D
Mechanical Features
Electrical life:8,000
Mechanical life:20,000
Contact position indicator: Yes
Protection degree:IP20
Reference temperature for setting of thermal element:30ºC
Ambient temperature (with daily average≤35ºC): -5ºC...+40ºC
Storage temperation: -25ºC...+70ºC
Installation
Terminal connection type: Cable/U-type busbar/Pin-type busbar
Terminal size top/bottom for cable: 25mm2 18-3AWG
Terminal size top/bottom for busbar: 25mm2 18-3AWG
Tightening torque 2.0 N*m 22 In-Ibs.
Mounting: On DIN rail EN 60715 (35mm) by means of fast clip device
Connection: From top and bottom
Combination with accessories
Auxiliary contact: Yes
Shunt release: Yes
Under voltage release: Yes
Alarm contact: Yes
1.Application
DZ47N-63 is applicable to a line of AC 50Hz/60Hz, 230V in single pole, 400V in double, three, four poles for protecting overload and short circuit, and rated current up to 63A. It can also be used for infrequent line conversion under the normal condition.The breaker is applicable to lighting distribution system in industrial enterprise, commercially district, high-rise building and dwelling house. It conforms with the standards of IEC60898.
2.Main Technical Parameter
Type |
DZ47N-63 |
Pole |
1P |
2P, 3P, 4P |
Rated current (A) |
6,10,16,20,25,32,40,50,63 |
Rated voltage(V) |
230 |
400 |
Ambient temperature |
-5oC~+40oC |
Type of instantaneous release |
C |
D |
C |
D |
Rated short circuit breaking capacity Icn(KA) |
1-32A: 6
50-63A: 4 |
4 |
1-32A: 6
50-63A: 4 |
4 |
3.Applicable conducting wire
Rated current(A) |
Norminal cross section of wire mm2 |
1-6A |
1 |
10A |
1.5 |
16,20A |
2.5 |
25A |
4 |
32A |
6 |
40,50A |
10 |
63A |
16 |
4.The over-current protection property
Ambient Temperature |
Initial Status |
Test Current |
Expected Result |
Expected Result |
Note |
30±2oC |
Cold position |
1.13In |
t≥1h |
Non-release |
- |
Carried out immediately after previous test |
1.45In |
t<1h |
Release |
- |
Cold position |
2.55In |
1s<t<60s (In≤32A) |
Release |
Current smoothly rises to specified value within 5s |
Cold position |
2.55In |
1s<t<120s (In>32A) |
Release |
-5~+40oC |
Cold position |
3In |
t≥0.1s |
Non-release |
Type B |
Cold position |
5In |
t<0.1s |
Release |
Type B |
Cold position |
5In |
t≥0.1s |
Non-release |
Type C |
Cold position |
10In |
t<0.1s |
Release |
Type C |
Cold position |
10In |
t≥0.1s |
Non-release |
Type D |
Cold position |
20In |
t<0.1s |
Release |
Type D |