1.Application
DZ48N-63 miniature circuit breaker is applicable to a line of AC 50Hz/60Hz, 230V in singlepole, 400V in double, three, four poles for protecting overload and short circuit, and rated cur-rent up to 63A. It can also be used for infrequent line conversion under the normal condition.Thebreaker is applicable to lighting distribution system in industrial enterprise, commercially district,high-rise building and dwelling house. It conforms with the standards of IEC60898.
2.Main Technical Parameter
Type | DZ48N-63 | |||||
---|---|---|---|---|---|---|
Pole | 1P | 2P, 3P, 4P | ||||
Rated current (A) | 6,10,16,20,25,32,40,50,63 | |||||
Rated voltage(V) | 230 | 400 | ||||
Type of instantaneous release | C | D | C | D | ||
Rated short circuit breaking capacity Icn(KA) | 1-40A: 6 50-63A: 4.5 |
4.5 | 1-40A: 6 50-63A: 4.5 |
4.5 | ||
Life (times) | 1-32A | Electric life | 4000 | |||
Mechanical life | 6000 | |||||
Operation frequency | 240 times per hour | |||||
40-63A | Electric life | 4000 | ||||
Mechanical life | 6000 | |||||
Operation frequency | 120 times per hour |
3.Applicable conducting wire
Rated current(A) | Nominal cross section of wire mm2 |
1-6A | 1 |
10A | 1.5 |
16,20A | 2.5 |
25A | 4 |
32A | 6 |
40,50A | 10 |
63A | 16 |
4.The over-current protection property
Ambient Temperature | Initial Status | Test Current | Expected Result | Expected Result | Note |
---|---|---|---|---|---|
30±2oC | Cold position | 1.13In | t≥1h | Non-release | - |
Carried out immediately after previous test | 1.45In | t<1h | Release | - | |
Cold position | 2.55In | 1s<t<60s (In≤32A) |
Release | Current smoothly rises to specified value within 5s | |
Cold position | 2.55In | 1s<t<120s (In>32A) | Release | ||
-5~+40oC | Cold position | 3In | t≥0.1s | Non-release | Type B |
Cold position | 5In | t<0.1s | Release | Type B | |
Cold position | 5In | t≥0.1s | Non-release | Type C | |
Cold position | 10In | t<0.1s | Release | Type C | |
Cold position | 10In | t≥0.1s | Non-release | Type D | |
Cold position | 20In | t<0.1s | Release | Type D |