Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Electric Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Environment conditions for operation:
|
Environmental temperature Tempeerature condition:-5oC ~+40oC ;the average value within 24h shall not exceed +35(Speial situation excluded )Elevation Altnmosphere condition Relative humidity at +40oC. shall not exceed 50%.higher hum-idity is permissible at lower temperature condition. when the highest monthly average relative humidity is 90% in the humiddext month,the lowest monthly average temperature of this month is +25oC.And consider the influence of dew on product surface due to temperature changes.pollution grade:grade The breaker should be installed caccording to the requirements on the instruction manual.The vertical inclination degree shall not exceed 5o |
Structure:
|
The breaker consists of body and drawer base.inserting the body into the drawer base, thus make the drawer-type breaker |
Installation and usage :
|
Installation Unload the breaker from the soleplate of package-box. if it is drawer type,firstly pull out the handle from under the drawer-base of breaker,and plug it into the hole on central section of plastic cover under the drawer-base crossbeam,anticlockwise turns the handle,breaker body will slowly slide along the outside of drawer-base. When the guide-rod points to separated position and handle can't be rotated any longer,pull out the handle and firmly grasp the aluminum hadle on drawer-base,pull out the breaker body and remove ift form drawer-base Check the insulation resistance with a 500V megger,resistance should not be less than 20MQ when ambient temperature is 20oC5oCand relative humidity is 50%-70%.otherwise have it drying. Put the breaker(fixed-type) or drawer-base(drawer-type) onto the installation- bracket,and make it fixed,directly connect the bus wire of main circuit to the bus wire of fixed-type circuit breaker,alternatively put breaker body onto the guild rail of drawer-base.Plug the place,then connect the bus wire of main circuit to bus wire of drawer-base. wiring the secondary circuit according to electric principle diagram. Note:something like bolts,nuts.gaskets shouldn't be left inside the drawer-base to avoid being blocked. Usage and operation Check the rated voltage of the following components whetherconforms to the power voltage or not .such as under voltage release,shunt releaseclosing electromagnet,motor-driven mechanism and intelligent controller Maintenance Check the technical index on time or and some lubricating oil.,etc. This breaker structure is arranged vertically and modularized composition with each function=cell separated,which make the maintenance easy.it has compact structure,reliable operation and strong free maintenance capability. P lease check the technical parameters on the nameplate accordance with the reauirements of order before installation |
Product model and its meaning :
|
|
Making the secondary circuit power,the motor-driven menchanism can store eenergy automatically until hearing the click and energy stored "indicating on the panel. otherwise press the storage handle for 6 times until hearing the click and the indicator display energy stored" and the closing operation can be realized either by closing electromagnet or manual button. |
|
DW45-1000 |
Main teachnical parameter:
|
Rated ultimate short circuit breaking capacity(KA) | lcu=42KA 400V 20KA 690V lcu=lcw=30KA 400V 15KA 690V |
|
Rated current in (A) | 200 400 630 800 1000 | |
Number of poles | 3,4 | |
Rated voltage ue(V) | 400V,690V | |
Rated insulation voltage Ui (A) | 1000V | |
Rated current of N-pole IN(A) | 50%In,100%IN | |
Fixed disconnection time | 23-32Ms | |
Intelligent controller | sandard type(M) | |
Communication type(H) | ||
Operation performance | Electric life | 500 |
mechanical life | Non-maintenance 2500 | |
Maintenance 10000 | ||
Connection pattern | Horizontal,vertical |
DW45-2000 |
Main teachnical parameter:
|
Rated ultimate short circuit breaking capacity(KA) | lcu=80KA 400V 50KA 690V lcs=lcw=50KA 690V 40KA 690V |
|
Rated current in (A) | 400 630 800 1000 1250 1600 2000 | |
Number of poles | 3,4 | |
Rated voltage ue(V) | 400V,690V | |
Rated insulation voltage Ui (A) | 1000V | |
Rated current of N-pole IN(A) | 50%In,100%IN | |
Fixed disconnection time | 23-32Ms | |
Intelligent controller | sandard type(M) | |
Communication type(H) | ||
Operation performance | Electric life | 500 |
mechanical life | Non-maintenance 2500 | |
Maintenance 10000 | ||
Connection pattern | Horizontal,vertical |
DW45-3200 DW45-4000 |
Rated ultimate short circuit breaking capacity(KA) | lcu=100KA 400V 80KA 690V lcs=lcw=80KA 400V 40KA 690V |
|
Rated current in (A) | 2000 2500 3200 4000 | |
Number of poles | 3, 4 3 | |
Rated voltage ue(V) | 400V,690V | |
Rated insulation voltage Ui (A) | 1000V | |
Rated current of N-pole IN(A) | 50%In,100%IN | |
Fixed disconnection time | 23-32Ms | |
Intelligent controller | sandard type(M) | |
Communication type(H) | ||
Operation performance | Electric life | 500 |
mechanical life | Non-maintenance 2500 | |
Maintenance 10000 | ||
Connection pattern | Horizontal,vertical |
DW45-6300 |
Rated ultimate short circuit breaking capacity(KA) | lcu=120KA 400V 80KA 690V lcs=lcw=100KA 400V 60KA 690V |
|
Rated current in (A) | 4000 5000 6300 | |
Number of poles | 3, 4 3 | |
Rated voltage ue(V) | 400V,690V | |
Rated insulation voltage Ui (A) | 1000V | |
Rated current of N-pole IN(A) | 50%In,100%IN | |
Fixed disconnection time | 23-32Ms | |
Intelligent controller | sandard type(M) | |
Communication type(H) | ||
Operation performance | Electric life | 500 |
mechanical life | Non-maintenance 2500 | |
Maintenance 10000 | ||
Connection pattern | Horizontal,vertical |